ABB PowerValue 2KVA

ABB’s PowerValue11 RT is a double-conversion online UPS that guarantees clean, reliable power for your critical single-phase applications. As well as maintaining power to your
servers, point-of-sale terminals, workstation clusters, routers, switches, hubs and sensitive electronic equipment, the PowerValue11RT also conditions incoming power to eliminate spikes, swells, sags, noise and harmonics.


The PowerValue11 RT can be used as a standalone UPS device or installed into a standard 19″rack configuration, with connectivity options available.

SKU: PV-11RT2K Categories: ,

High reliability
• Reliable double conversion topology protects load from all input disturbances
• Batteries can be added or replaced easily
• Reduced recovery time from discharge
• Redundant parallel operation available (6 and 10 kVA units)

Low cost of ownership
• Scalable runtime
• High operating efficiency, regardless of loading
• Reduced installation and upgrading costs
• Compact design

Flexible design
• Configurable in tower or rack-mount format
• Rotatable display
• UPS can be connected with up to four parallel battery modules for extended runtime
• Long backup models available
• Full set of accessories and connectivity options

Efficient service concept
• Manually operated maintenance bypass switch (optional)
• Easy set up and maintenance (plug and play)
• User-friendly display
• Hot swap user-replaceable batteries

GENERAL DATA 2kVA
Output rated power 2kVA/18
00 W
Output power factor 0.9
Topology Online double conversion
Parallel configuration No
Inbuilt batteries Yes (standard UPS) Long Run UPS has no internal battery

INPUT
Nominal input voltage
208/220/230/240 VAC
Input voltage tolerance 120-276 VAC (load dependent)
Input current THDi <5% with full resistive load
Frequency range 45-55 Hz / 54-66 Hz
Power factor ≥0.99

OUTPUT
Rated output voltage
208/220/230/240 VAC
Voltage tolerance ±1% (referred to 230V)
Voltage distortion ≤2% linear load, ≤5% non linear load
Overload capacity (linear load) on inverter

12s: 102-129% load
1.5s: 130-150% load
100ms: ≥ 150% load

Nominal frequency 50 or 60 Hz
Crest factor 3:1 (load supported)

EFFICIENCY
Overall system efficiency
Up to 93%
In eco-mode Up to 95%

ENVIRONMENT
Protection rating
IP20
Storage temperature UPS: -25°C to 60°C; Batteries: 0°C to 35°C
Operating temperature 0°C to 40°C
Relative humidity 0% to 95%
Altitude (above see level) 1000m without derating

BATTERIES
Type
VRLA (valve regulated lead-acid)
Inbuilt batteries 4x9 Ah
Charging current 1.5A Standard /6A Long Run
Recharge time (inbuilt batteries) 3h to 90%

COMMUNICATIONS
User interface
LCD display
Optional communication cards SNMP;ModBus;AS400;Environmental monitoring sensor probe

STANDARDS
Safety
IEC/EN 62040-1
EMC IEC/EN 62040-2
Performance IEC/EN 62040-3
Manufacturing ISO 9001:2015, ISO 14001:2015, OHSAS 18001

WEIGHT, DIMENSIONS
Weight
19.7kg Standard UPS 9.3kg Long Run UPS
Dimensions w x h x d 438×86.5(2U)x436mm

UPS Brochure

UPS Manual

 

Rail Kit

Extended battery pack (Link)

Network card

Bypass Switch – (Link)